What Wire Gauge Do I Need Based on Amperage and Distance?
Calculate electrical wire gauge (mm²) by amperage, distance, and voltage. Prevent voltage drop over 3%. Includes breaker sizing recommendations.
- Asociación Electrotécnica Argentina data · July 2026 · Martín Rodríguez
More info
- Formula verified by automated tests
- Private — runs on your device
See step-by-step calculation
See this calculation step by step
See period-by-period detail
How to use this calculator
Follow this tool’s steps, then review its formula, assumptions, and limits below.
When to use this calculator
- Installing an air conditioning unit in a room far from the electrical panel — determining the correct wire size.
- Doing the electrical wiring for a house addition or new construction.
- Adding a new circuit for an electric oven, water heater, or motor.
- Your circuit breaker keeps tripping and you want to know if the wire is undersized.
- Licensed electrician preparing project plans and technical specifications.
Copper wire ampacity by gauge (AEA 90364)
| Gauge (mm²) | Ampacity in conduit (A) | Ampacity open air (A) | Typical circuit / use |
|---|---|---|---|
| 1.5 | 14 | 19 | Standard lighting (IU circuits) |
| 2.5 | 21 | 26 | Standard outlets (TU circuits, 4,400 W at 220V) |
| 4.0 | 28 | 36 | Air conditioning, general outlets (TUG) |
| 6.0 | 36 | 45 | Electric ovens, water heaters |
| 10.0 | 50 | 63 | Kitchen/laundry special circuits (TUE) |
| 16.0 | 68 | 85 | Main service entrance — small house (≤ 40 A) |
| 25.0 | 89 | 112 | Main service entrance — medium/large house |
| 35.0 | 110 | 140 | Multi-unit building service distribution |
Source: AEA 90364 — Argentine Electrotechnical Association Electrical Installation Standards. Values for copper conductors at 70°C rated temperature, PVC insulated.
How it works
Formulas
Voltage drop (single-phase 220V)
ΔV = 2 × L × A × ρ / S
Where:
ΔV = voltage drop (V)
L = cable length (m, one direction)
A = amperage (A)
ρ = copper resistivity = 0.0178 Ω·mm²/m at 20°C
S = conductor cross-section (mm²)
2 = factor for round-trip current pathFor three-phase 380V
ΔV = √3 × L × A × ρ / SSolving for wire gauge
S = (2 × L × A × ρ) / ΔV_maxWhere ΔV_max = V × (maxDropPercent / 100) → for 220V and 3%: ΔV_max = 6.6 V.
Wire ampacity by gauge (AEA 90364)
| Gauge (mm²) | Capacity A (in conduit) | Capacity A (open air) | Typical use |
|---|---|---|---|
| 1.0 | 10 | 14 | Small lighting circuits |
| 1.5 | 14 | 19 | Standard lighting (IU) |
| 2.5 | 21 | 26 | Standard outlets (TU) |
| 4.0 | 28 | 36 | Air conditioning, general outlets (TUG) |
| 6.0 | 36 | 45 | Electric ovens, water heaters |
| 10.0 | 50 | 63 | Kitchen circuits, special outlets (TUE) |
| 16.0 | 68 | 85 | Main service entrance (small house) |
| 25.0 | 89 | 112 | Main service entrance (large house) |
| 35.0 | 110 | 140 | Multi-unit building service |
| 50.0 | 134 | 170 | Generator connection |
| 70.0 | 171 | 215 | Industrial distribution panels |
| 95.0 | 207 | 260 | Industrial distribution |
Residential circuit classifications per AEA
| Circuit type | Wire gauge | Breaker | Typical load |
|---|---|---|---|
| IUA (general lighting) | 1.5 mm² | 10 A | 1,500 W lighting |
| IUG (general lighting) | 1.5 mm² | 10 A | 1,500 W lighting |
| TUA (standard outlets) | 2.5 mm² | 20 A | 4,400 W (computers, TVs) |
| TUG (general outlets) | 2.5 mm² | 20 A | 4,400 W |
| TUE (kitchen/laundry special) | 4.0 mm² | 25 A | 5,500 W (washer, microwave) |
| Air conditioning | 4.0–6.0 mm² | 20–25 A | 4,500–5,500 W |
| Electric water heater | 4.0–6.0 mm² | 25 A | 5,500 W |
| Electric oven | 6.0 mm² | 32 A | 7,000 W |
| Main service entrance | 16 mm² | 40–63 A | Whole house |
Voltage, amperage, and power
P (W) = V × A (single-phase)
P (W) = √3 × V × A × cos(φ) (three-phase)
A = P / V
Residential examples:
100 W light bulb at 220V → 0.45 A
LED TV 150 W → 0.68 A
Microwave 1,200 W → 5.45 A
Water heater 2,200 W → 10.0 A
Electric oven 3,500 W → 15.9 A
AC unit 3,000 BTU 1,200W → 5.45 A
Electric range 7,000 W → 31.8 A (very high!)Why voltage drop matters
Voltage drop is the loss of voltage along the wire due to its electrical resistance. If you have 220V at the panel but only 210V reaches the equipment, that's a 10V drop = 4.5%.
Problems from excessive voltage drop
Maximum allowable drop (AEA standards)
| Application | Max voltage drop |
|---|---|
| Residential | 3% |
| Commercial | 4% |
| Industrial | 5% |
| Motor starting (inrush) | 6% |
| Sensitive equipment (servers, UPS) | 1% |
Circuit breaker selection
The circuit breaker (or thermal breaker) protects the wire from overheating. It must satisfy:
A_equipment ≤ A_breaker ≤ A_wire_capacityExample: 15 A equipment, 2.5 mm² wire (21 A capacity) → 16 A breaker (next size above equipment, below wire capacity).
Standard breaker sizes (A): 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160.
Differential breaker (RCD/GFCI)
Every residential installation must have a differential breaker of 30 mA (mandatory by AEA). It protects against electrocution by cutting power if current leaks to ground. It does not replace the thermal breaker — they work together.
Wire color codes per AEA
| Color | Function |
|---|---|
| Brown / Black | Live (phase), 220V |
| Light blue | Neutral |
| Green/yellow striped | Ground (earth) |
| Red / Gray | Second phase (split-phase or three-phase) |
True ground is always green-and-yellow stripe. A wire that's only green or only yellow is not ground.
Wire types
| Type | Application |
|---|---|
| NYM / NYA | Fixed in-wall installations |
| Flexible workshop cable | Temporary runs, appliance cords |
| Underground cable | Buried runs, extra insulation |
| Fire-resistant | High-rise buildings (smoke reduction) |
| Bare copper/aluminum | Ground connections, inside conduit |
| Armored (MC) | Industrial, high-interference areas |
Indicative pricing (Argentina 2026)
| Wire size | Cost per meter (100m spool) |
|---|---|
| 1.5 mm² | $800 – $1,200 |
| 2.5 mm² | $1,200 – $1,800 |
| 4 mm² | $1,800 – $2,800 |
| 6 mm² | $2,500 – $3,800 |
| 10 mm² | $4,000 – $5,500 |
| 16 mm² | $6,000 – $8,500 |
Common brands: Imsa, Pirelli, Delcable, Prysmian.
Installation tips
1. Never overload an outlet: avoid power strips for air conditioners or microwaves.
2. Wires in conduit: cables run inside plastic or rigid conduit.
3. No splices inside conduit: splices only in junction boxes.
4. Strict color code: professional electricians always follow AEA colors.
5. Subpanel for large loads: homes over 1,000 sq ft benefit from a second panel near heavy users (kitchen, laundry).
6. Inspect every 5 years: wire insulation degrades; check for loose connections and heat.
Common residential setups
Small house (70 m² / 750 sq ft)
Medium house (150 m² / 1,600 sq ft)
Common mistakes
1. Oversizing for false safety: jumping from 1.5 to 4 mm² is wasteful. Use the AEA table.
2. Ignoring distance: 30 m with 2.5 mm² at 20 A causes over 5% drop (non-compliant).
3. Breaker larger than wire: NEVER. If wire is 2.5 mm² (21 A capacity), max breaker is 20 A.
4. Skipping the differential: not optional — it's a legal and safety requirement.
5. Poor ground connections: most older houses have inadequate grounding. Test with a ground meter.
Real-world example: wire for a 3,000 BTU air conditioner (1,200 W consumption) 25 m from the breaker panel
Frequently asked questions
How do I know what wire gauge I need for my circuit?
How many amps can a 2.5 mm² wire safely handle?
What is voltage drop and why does it matter?
How far can I run 2.5 mm² wire at 15 amps before voltage drop becomes a problem?
Should I use copper or aluminum wire for my home electrical installation?
What's the difference between single-phase (220V) and three-phase (380V) electrical service?
Why does my circuit breaker keep tripping?
Is a GFCI (differential) breaker really necessary?
What happens if I use undersized wire for my circuit?
What are the electrical wire color codes, and why do they matter?
Sources & references
- AEA 90364 - Electrical Installation Standards — Asociación Electrotécnica Argentina
- ENRE - Technical Standards — ENRE
- IRAM 2183 - PVC Insulated Cables — IRAM
- Prysmian - Technical Cable Catalog — Prysmian
Methodology & trust
Construction calculator with its formula verified automatically against AEA 90364 - Electrical Installation Standards, per our editorial policy and methodology.
Updated: July 2026. Parameters are verified periodically against the cited sources.
Calculations run 100% in your browser. We do not store or transmit your data.
Indicative results. For critical decisions, consult a professional.
Rodríguez, M. (2026). What Wire Gauge Do I Need Based on Amperage and Distance?. Hacé Cuentas. https://hacecuentas.com/en/electricidad-cable-amperaje-seccion
Content licensed under CC-BY 4.0 — reuse it citing the source with a link to Hacé Cuentas.