Electronics

AWG Wire Size Chart & Calculator by Amperage

Calculator Free · Private
Reviewed by: (política editorial ) · Last reviewed:
Was this calculator helpful?

The AWG (American Wire Gauge) system is an inverse logarithmic scale: the higher the number, the thinner the wire. Every 6 gauge steps, the cross-sectional area halves. AWG 14 (2.08 mm²) is the minimum for 15 A household branch circuits per the NEC (National Electrical Code); AWG 12 (3.31 mm²) is required for 20 A kitchen circuits. Undersizing wire causes resistive heating, insulation damage, and fire hazards. This calculator applies NEC 310.15 ampacity tables and the standard 80%/125% derating rule for continuous loads.

Last reviewed: June 3, 2026 Verified by Source: NFPA 70 – National Electrical Code (NEC), Article 310: Conductors for General Wiring, NIST – American Wire Gauge (AWG) Standard, Handbook 100, Wikipedia – American Wire Gauge 100% private

AWG wire size by ampacity (75°C copper, NEC): **AWG 14 = 15 A**, AWG 12 = 20 A, AWG 10 = 30 A, AWG 8 = 40 A, AWG 6 = 55 A, AWG 4 = 70 A, AWG 2 = 95 A. For continuous loads (≥3 hours), multiply the load by 1.25 before selecting the gauge — e.g., 16 A continuous → AWG 12 (20 A rated). Higher AWG number = thinner wire.

When to use this calculator

  • Sizing residential branch circuits: AWG 14 (15 A) or AWG 12 (20 A) per NEC 210.52.
  • Selecting wire gauge for a 240 V electric dryer drawing 30 A — requires AWG 10 minimum.
  • Solar panel wiring: correct gauge for a 40 A DC string combiner run to avoid >2% voltage drop.
  • Automotive wiring: choosing AWG for a 60 A alternator output cable with temperature derating.
  • Industrial motor feeder sizing: applying NEC 430.22 for a 20 HP, 230 V single-phase motor.

Worked Example — 15 A Bedroom Circuit

  1. Input: 15 A, General installation (75°C)
  2. Lookup: AWG 14 is rated 15 A at 75°C (NEC Table 310.15(B)(16))
  3. Cross-section: 2.08 mm² — diameter: 1.63 mm
  4. If load is continuous (≥3 h): 15 A × 1.25 = 18.75 A → upsize to AWG 12 (20 A)
Result: AWG 14 = 2.08 mm² (1.63 mm diameter) — non-continuous 15 A circuits

How it works

3 min read

AWG Wire Size by Amperage — Quick Reference Table

AWGDiameter (mm)Area (mm²)Max 60°CMax 75°CMax 90°CTypical Use
181.020.827 A10 A14 ALow-voltage lighting
161.291.3110 A13 A18 AExtension cords
141.632.0815 A20 A25 A15 A branch circuits
122.053.3120 A25 A30 A20 A kitchen circuits
102.595.2630 A35 A40 ADryers, A/C units
83.268.3740 A50 A55 ARanges, EV chargers
64.1113.3055 A65 A75 A60 A subpanels
45.1921.1570 A85 A95 ALarge HVAC feeders
26.5433.6295 A115 A130 A100 A service entry
1/08.2553.48125 A150 A170 A150 A service entry
2/09.2767.43145 A175 A195 A200 A service panels

Single copper conductor, per NEC Table 310.15(B)(16).

---

How It Is Calculated

The AWG scale is defined by two anchor points: AWG 0000 (4/0) = 0.46 inches diameter and AWG 36 = 0.005 inches diameter, with 39 steps in between. Every 6 gauge steps, the cross-sectional area halves (or doubles going down).

Core Formula — AWG to Physical Dimensions

Diameter (inches) = 0.005 × 92^((36 − AWG) / 39)
Diameter (mm)     = 25.4 × Diameter (inches)
Area (mm²)        = π/4 × Diameter(mm)²
               OR = 0.012668 × 92^((36 − AWG) / 19.5)

Ampacity Derating for Continuous Loads (NEC 210.19 / 310.15)

For continuous loads (≥3 hours): Required Ampacity = Load (A) × 1.25

Example: A 15 A continuous load requires a conductor rated for at least 18.75 A, so AWG 12 (20 A rated) is selected, not AWG 14 (15 A rated).

---

Common Sizing Scenarios

15 A Household Circuit


Non-continuous 15 A at 120 V: AWG 14 (2.08 mm², 1.63 mm diameter). Protected by a 15 A breaker.

20 A Kitchen Circuit


NEC 210.11(C)(1) mandates 20 A small-appliance circuits: AWG 12 (3.31 mm²). Protected by a 20 A breaker.

30 A Electric Dryer (240 V)


Running current 24 A × 1.25 (continuous) = 30 A. AWG 10 (5.26 mm²) at 75°C column satisfies this. Paired with a 30 A double-pole breaker.

40 A Solar Combiner (DC, 50 ft)


String current 32 A. For <2% voltage drop at 48 V over 100 ft round trip: AWG 8 (8.37 mm²) handles both ampacity and drop.

---

Common Sizing Errors

1. Ignoring the continuous load rule (×1.25): A 16 A continuous load needs AWG 12, not AWG 14.
2. Mixing temperature ratings: Using the 90°C column when terminals are rated 60°C or 75°C — NEC 110.14(C) requires the lowest rating in the circuit.
3. Forgetting conduit fill derating: 4–6 conductors in conduit = 80%; 7–9 = 70%; 10–20 = 50%.
4. Confusing AWG with mm² (IEC): AWG 14 = 2.08 mm², not 1.5 mm². They are not interchangeable.
5. Ignoring voltage drop on long runs: Ampacity tables prevent overheating, not voltage sag. Calculate ΔV = 2 × L × I × R for runs over 100 ft.

Frequently asked questions

What does AWG stand for, and why does a larger number mean a thinner wire?

AWG stands for American Wire Gauge, a standardized system dating to 1857. The numbering reflects the number of drawing dies needed: more draws = thinner wire = higher number. AWG 4/0 (thickest common size) = 11.68 mm diameter; AWG 36 = 0.127 mm. Every 6 AWG steps, the cross-sectional area halves.

What AWG wire do I need for 15 amps?

For a standard 15 A non-continuous circuit (e.g., a bedroom outlet), you need AWG 14 (2.08 mm², diameter 1.63 mm), protected by a 15 A breaker. If the load runs continuously for 3+ hours, multiply by 1.25 — 15 A × 1.25 = 18.75 A — and you'd need AWG 12 (20 A rated).

What AWG wire do I need for 20 amps?

AWG 12 (3.31 mm², diameter 2.05 mm) is required for 20 A circuits. AWG 14 is explicitly prohibited on 20 A breaker circuits. NEC 210.11(C)(1) mandates AWG 12 for kitchen small-appliance branch circuits.

How does the NEC 80% (125%) rule affect wire sizing for continuous loads?

Per NEC 210.19(A)(1), any load operating for 3+ hours must be calculated at 125% of actual current. Equivalently, a wire may only carry 80% of its rated ampacity for continuous loads. Example: a 16 A continuous load requires a 20 A-rated conductor — AWG 12, not AWG 14.

What is the difference between AWG 14 and 1.5 mm² wire? Can I substitute them?

No — they are NOT interchangeable. AWG 14 = 2.08 mm², which is larger than the European IEC 1.5 mm² (diameter 1.38 mm). The closest metric equivalent to AWG 14 is 2.5 mm². Substituting 1.5 mm² for AWG 14 in a 15 A circuit creates a fire hazard and violates NEC.

Does aluminum wire need a different AWG than copper?

Yes. Aluminum has ~61% the conductivity of copper, so it must be sized about 2 AWG numbers larger. AWG 12 copper = 20 A (75°C); AWG 12 aluminum = only 15 A. For a 20 A aluminum circuit, use AWG 10. Aluminum also requires anti-oxidant compound and CO/ALR-rated devices per NEC 310.106(B).

How do I calculate voltage drop for a long wire run?

ΔV = 2 × L × I × R_per_ft, where L is one-way run length and R_per_ft is conductor resistance (AWG 12 copper = 0.001588 Ω/ft; AWG 10 = 0.000999 Ω/ft). For a 100 ft run at 15 A on AWG 12: ΔV = 2 × 100 × 15 × 0.001588 = 4.76 V (~4% of 120 V). To stay under 3%, upsize to AWG 10.

Can I use the same AWG wire for DC circuits (solar, EV) as for AC circuits?

The physical wire is identical, but code requirements differ. NEC Article 690 (Solar PV) and Article 625 (EV charging) apply to DC. DC arcing does not self-extinguish at zero-crossing like AC, so OCPD ratings and insulation voltage ratings must be verified separately. AWG 10 rated for 30 A AC can be used on a 30 A DC solar string, but verify breaker and conduit requirements.

Sources and references